Fluke 1507 for Rent, 1kV Insulation Resistance Tester, 0.01Mohms-10Gohms
1kV Insltn.Resist.Tester 0.01Mohms-10Gohms
Order #: 1507-RENT1
Mfg #: 1507-RENT1
Call for price
Call for price
Fluke 1507 for Rent, 1kV Insulation Resistance Tester, 0.01Mohms-10Gohms
1kV Insltn.Resist.Tester 0.01Mohms-10Gohms
Order #: 1507-RENT1
Mfg #: 1507-RENT1
Product Highlights
- Insulation test range: 0.01 MΩ to 10 GΩ
- Insulation test voltages: 50 V, 100 V, 250 V, 500 V, 1000 V
- Save both time and money with Automatic calculation of Polarization Index and Dielectric Absorption Ratio
- Make repetitive tests simple and easy with the 1507’s Compare (Pass/Fail) function
- Repetitive or hard-to-reach testing is easy with the remote test probe
- Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
- Auto-discharge of capacitive voltage for added user protection
- AC/DC voltage: 0.1 V to 600 V
- 200 mA Continuity
- Resistance: 0.01 Ω to 20.00 kΩ
- Save battery power with auto power off
- Read measurements easily with large, backlit display
- CAT IV 600 V overvoltage category rating for added user protection
- Remote probe, test leads, probes and alligator clips included with each tester
- Accepts optional Fluke TPAK magnetic hanging system to free your hands for other work
- Four AA alkaline batteries (NEDA 15 A or IEC LR6) for at least 1000 insulation tests
- One year warranty
- Coded
AC/DC Voltage Measurement | ||
Accuracy | Range | 600.0 V |
Resolution | 0.1 V | |
50 Hz to 400 Hz ± (% of Rdg + Digits) | ±(2% + 3) | |
Input impedance | 3 MΩ (nominal), < 100 pF | |
Common mode rejection ratio (1 kΩ unbalanced): | > 60 dB at DC, 50 or 60 Hz | |
Overload protection | 600 V rms or DC | |
Earth Bond Resistance Measurement | ||
Range/Resolution | 20.00 Ω | 0.01 Ω |
200.0 Ω | 0.1 Ω | |
2000 Ω | 1.0 Ω | |
20.00 kΩ | 0.01 kΩ | |
Accuracy | ±(1.5% + 3) | |
Overload protection | 2 V rms or DC | |
Open circuit test voltage | > 4.0 V, < 8 V | |
Short circuit current | > 200.0 mA | |
Insulation Specifications | ||
Measurement range | 0.01 MΩ to 10 GΩ | |
Test voltage | 50 V, 100 V, 250 V, 500 V, 1000 V | |
Test voltage accuracy | + 20%, - 0% | |
Short circuit current | 1 mA nominal | |
Auto discharge | Discharge time < 0.5 second for C = 1 µF or less | |
Live circuit indicator | Inhibit test if terminal voltage > 30 V prior to initialization of test | |
Maximum capacitive load | Operable with up to 1 µF load | |
Measure accuracy | 50 V | ±(3% + 5) |
100 V | ±(3% + 5) | |
250 V | ±(1.5% + 5) | |
500 V | ±(1.5% + 5) | |
1000 V | ±(1.5% + 5) to 2000 MΩ, ±(10% + 3) above 2000 MΩ | |
General Specifications | ||
Maximum voltage applied to any terminal: | 600 V AC rms or DC | |
Storage temperature | -40°C to 60°C (-40°F to 140°F) | |
Operating temperature | -20°C to 55°C (-4°F to 131°F) | |
Temperature coefficient | 0.05 x (specified accuracy) per °C for temperatures < 18°C or > 28°C (< 64°F or > 82°F) | |
Relative humidity | ||
0% to 95% @ 10°C to 30°C (50°F to 86°F) | ||
0% to 75% @ 30°C to 40°C (86°F to 104°F) | ||
0% to 40% @ 40°C to 55°C (104°F to 131°F) | ||
Vibration | Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument | |
Shock | 1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor) | |
Electromagnetic compatibility | In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997) | |
Safety | Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V (CAT IV) | |
Certifications | CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition | |
Batteries | Four AA batteries (NEDA 15A or IEC LR6) | |
Battery life | Insulation test use: | Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. |
Resistance measurements: | Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1 Ω with a duty cycle of 5 seconds on and 25 seconds off. | |
Size (H x W x L) | 5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in) | |
Weight | 550 g (1.2 lb) | |
IP rating | IP40 | |
Altitude | Operating | 2000 m CAT IV 600 V, 3000 m CAT III 600 V |
Non-operating (storage) | 12,000 m | |
Over-range capability | 110% of range | |
Included accessories | TL224 Test Leads, TP74 Test Probes, clips PN 1958654 (red) and PN 1958646 (black), holster and remote probe |